GTYQ-TGD02W Stand-alone Combustible Gas Detector
Working voltage: Powered by a rechargeable polymer lithium battery pack with a rated voltage of 7.4 V
Power: <6 mW (non-alarm state)
Operating temperature: -20 ℃ to +70 ℃
Display mode: Color LCD display
Detection method: continuous operation
Detection device: infrared detection type
Sampling method: natural diffusion
Detection object: Combustible gases in the air
Alarm point: Low alarm defaults to 25% LEL (adjustable), high alarm defaults to 50% LEL
Detection range: 3~100% LEL
Detection accuracy: indication deviation not exceeding ± 5% FS
Communication method: Standalone models use wireless LoRa communication by default (optional LoRa communication board and communication antenna are required, with an effective communication distance of 200 meters in open and unobstructed environments).
Remote control function: optional
Output form: Passive switch quantity
Response time: <15 s
Sound and light alarm function: optional
Weight: 2.5 kg
Overall dimensions: 250 × 125 × 65 mm (with sound and light)